System Components Archives - www.elektrotehnika.mk https://elektrotehnika.mk Се од електрика за вашиот дом Wed, 22 Jun 2022 12:39:21 +0000 mk-MK hourly 1 https://wordpress.org/?v=6.0.14 MTN680329 KNX System Componets https://elektrotehnika.mk/shop/mtn680329-knx-system-componets/ Thu, 09 Jul 2020 14:07:38 +0000 http://elektrotehnika.mk/?post_type=product&p=10565 Main
The KNX/IP router enables telegrams to be forwarded between different lines via LAN (IP) as a rapid backbone. The
device can additionally serve as a programming interface in order to connect a PC with the KNX bus (e.g. for ETS programming with suitable ETS).
Complementary
The IP address can be assigned dynamically via a DHCP server or via manual configuration (ETS parameter). The
device operates in accordance with the KNXnet/IP specification using Core, device management, tunnelling and routing.
The KNX/IP router forwards telegrams in both directions whilst taking a filter table into account and can buffer up to
150 telegrams.
For installation on DIN rails EN 50022. The bus is connected using a bus connecting terminal; a data rail is not necessary.
Supply voltage: DC 12-30 V (at DC 24 V 40 mA), AC 12-24 V
Device width: 2 modules = approx. 36 mm
Contents: With bus connecting terminal.
Colour: light grey

The post MTN680329 KNX System Componets appeared first on www.elektrotehnika.mk.

]]>
The post MTN680329 KNX System Componets appeared first on www.elektrotehnika.mk.

]]>
MTN680204 KNX System Componets https://elektrotehnika.mk/shop/mtn680204-knx-system-componets/ Wed, 27 May 2020 12:52:27 +0000 http://elektrotehnika.mk/?post_type=product&p=10255 For logical connection and electrical isolation of lines and areas.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus
connecting terminal; a data rail is not necessary.
KNX software functions: The device can be used as a backbone / line coupler or as a
repeater for forming line segments in existing or new KNX systems. The function as a coupler
or repeater can be parameterised.
Functions as coupler
Use as a backbone or line coupler depending on the physical address. Reduction of the bus
load through the filter function (filter table). Support of the full address area (Group 0-31) with
filter function. Forwarding of physically addressed telegrams (line => main line, main line =>
line) can be parameterised. Forwarding of group telegrams (line => main line, main line =>
line) can be parameterised. Telegram repetitions in the event of transmission errors can be
set separately for group telegrams, broadcast telegrams and physically addressed telegrams.
Telegram confirmation for group telegrams and physically addressed telegrams can be parameterised
separately.
Functions as repeater
Expansion of a line to max. 4 line segments with up to 64 participants each (incl. line coupler
or repeater). Telegram repetitions in the event of transmission errors can be set separately for
group telegrams, broadcast telegrams and physically addressed telegrams. With repeaters,
the telegrams are always forwarded.
Device width: 2 modules = approx. 36 mm
Note: With the coupler/repeater 7116/1.1 application, the entire group address range from 0
to 31 can be used for the filter function of the coupler (support for extended group addresses).
This application requires ETS 4.1 or higher.
Contents: With 2 bus connecting terminals.

The post MTN680204 KNX System Componets appeared first on www.elektrotehnika.mk.

]]>