Socket with industrial relay; Coil voltage: AC 230 V; 4 changeover contacts

                                              

Name Value Unit
Conformity marking  CE   
Pollution degree (1)   
Rated voltage EN (1) [V]  250 
Rated surge voltage (1) [kV]  2.5  kV 
Pull-in time (typ.) [ms]  25  ms 
Mechanical life  20 x 106 switching operations   
Drop-out time (typ.) [ms]  25  ms 
Nominal input current (coil 20 °C)  8,3 mA   
Operating power  1.2 VA   
Input voltage range  VN -20 % ... +10 %   
Max. switching voltage  250 VAC   
Max. switching power (resistive)  1,250 VA AC / 150 VA DC   
Recommended minimum load  12 V / 100 mA   
Bounce time (typ) [ms]  ms 
Dielectric strength, contact-coil (AC, 1 min) [kVrms 1.5  kVrms 
Dielectric strength open contact (AC, 1 min) [kVrms kVrms 
Nominal input voltage (VN 230 VAC   
Max. continuous current  5 A   
Max. make current (resistive) at 10 % OT *  15 A / 4 s   
Rated power  1.2 VA   
Holding voltage  80 % of VN   
Release voltage  0.3 x V   
Switching power (max.) AC1 / AC15  1250VA / 300VA   
1-phase motor load AC3 [kW]  0.12  kW 
Min. switching load  12 V / 100 mA   
Electrical life  1 x 105 switching operations   
Degree of protection  RTII   
Connection technology (1)  CAGE CLAMP®  
Cross section from (1) [mm?]  0.34  mm? 
Cross section up to (1) [mm?]  1.5  mm? 
Cross section from (1) [AWG]  22  AWG 
Cross section up to (1) [AWG]  16  AWG 
Cross section up to (2) [mm?]  2.5  mm? 
Stripped length from (1) [mm]  mm 
Stripped length up to (1) [mm]  10  mm 
Stripped length (1) [in]  0.37  in 
Contact material  AgCe   
Weight [g]  96.592 
Width [mm]  31  mm 
Width [in]  1.22  in 
Height [mm]  73  mm 
Height [in]  2.874  in 
Length [mm]  97  mm 
Length [in]  3.819  in 
Storage temperature  -40 °C ... +80 °C   
Standards/Specifications  GL, UL 508   
Type of mounting  DIN 35 rail   
Ambient operating temperature at VN  -25 °C ... +70 °C   
Ambient operating temperature for UL ()  -25 °C ... +50 °C